CHINT NXCC Capacitor Contactor,
is a specialize device designe for safe and efficient switching of low-voltage capacitor banks in power factor correction systems.
With rate operational voltage up to 690 V and current ratings from 25 A to 170 A,
it minimizes inrush current using pre-charge resistors to protect capacitors and extend service life.
Built to IEC/EN 60947-4-1 standards, the NXCC series ensures reliable performance in reactive power compensation,
offering stable operation even under demanding industrial conditions.
- Standards: IEC/EN 60947-4-1
- Rated Operational Voltage (Ue): Up to 690 V
- Rated Insulation Voltage (Ui): 690 V
- Impulse Withstand Voltage (Uimp): 6 kV
- Rated Current (Ith): 25 A / 32 A / 43 A / 63 A / 95 A / 115 A / 150 A / 170 A
- Rated Operational Current (Ie, AC-6b):
- NXCC-25: 19 A
- NXCC-63: 52.5 A
- NXCC-170: 136.8 A
- Controlled Capacitor Capacity (kvar):
- 220/230 V: 7.2–52.1 kvar
- 380/400 V: 12.5–90 kvar
- 660/690 V: 21.7–156.3 kvar
- Coil Working Voltage:
- 110 V, 127 V, 220 V, 380 V, 415 V (50 Hz)
- Pick-up: 85–110% Us; Release: 20–75% Us
- Coil Capacity (VA):
- Start/Hold: 70/9.5 VA (NXCC-25) to 1000/91.2 VA (NXCC-170)
- Auxiliary Contacts:
- 25–115 A: 2NO+1NC or 1NO+2NC
- 150–170 A: 3NO+2NC or 2NO+3NC
- Capacity: AC-15: 230 V/2.7 A; 400 V/1.5 A | DC-13: 220 V/0.3 A
- Surge Current Suppression: 20 × Ie (resistor pre-charge circuit)
- Protection Degree: IP20 (front) / IP10 overall
- Environmental Conditions:
- Temperature: −35 °C to +70 °C (normal −5 °C to +40 °C)
- Altitude: ≤ 2000 m
- Humidity: ≤ 50% at +70 °C; up to 90% at +20 °C
- Pollution Degree: 3
- Installation Category: III
- Inclination: ≤ ±5° from vertical
- Shock/Vibration: No significant mechanical vibration allowed
- Mounting Options:
- NXCC-25~43: Screw or 35 mm DIN rail
- NXCC-63~115: Screw or 35/75 mm DIN rail
- NXCC-150~170: Screw mounting
- Applications:
- Power factor correction cabinets
- Reactive power compensation systems
- Industrial and commercial capacitor banks
- Electrical distribution systems